CHILLER &
COOLING TOWER
Catatan :
-
7.62 m3/hours
Rata-rata kondisi air Cooling Tower
Catatan : -
pH : 9, Conduct : 1053, TDS : 526
Rata-rata kondisi air coolng tower (aman)
Chiller 1
Report bulan juli
Running Hours
599 Hours Berjalan
Peforma Chiller
RLA : 54.0 %
Delta Evap : 2.38 C
Delta Conden : 2.44 C
Catatan
-
Chiller 2
Report bulan juli
Running Hours
599 Hours Berjalan
Peforma Chiller
RLA : 54.0 %
Delta Evap : 2.38 C
Delta Conden : 2.44 C
Catatan
-
Chiller 3
Report bulan juli
Running Hours
599 Hours Berjalan
Peforma Chiller
RLA : 54.0 %
Delta Evap : 2.38 C
Delta Conden : 2.44 C
Catatan
-
COMPRESSOR
Compressor A
Report bulan juli
Running Hours
599 Hours Berjalan
Average Outlet Pressure
6.93 bar
Catatan
-
Compressor B
Report bulan juli
Running Hours
599 Hours Berjalan
Average Outlet Pressure
6.93 bar
Catatan
-
Compressor C
Report bulan juli
Running Hours
599 Hours Berjalan
Average Outlet Pressure
6.93 bar
Catatan
-
REVERSE OSMOSIS (RO)
Product RO
12074 m3
66%
Reject RO
5066 m3
34%
Rata-rata pengujian air
Catatan
---
Filter Cartridge Mesin RO
0,1-0,3
Nilai delta pressure menandakan filter masih aman
AIR HANDLING SYSTEM (AHU)
AHU Spray Dryer
AHU Powder Blending
Catatan
Delta Pressure diatas final pressure ada AHU 2.1, 1.2, dan 4.1 Spray Dryer dan 3.1 Drymix
medium filter masih di Bawah final pressure
EFISIENSI STEAM
Efisiensi
Sama dengan bulan Juli
Catatan Steam :
---
KONSUMSI
HARIAN
Kwh/Ton produksi
1028,736
Ton Steam/ Ton Produksi
3,828
m3 N2/ Ton Produksi
69,334
m3 Water/ produksi
10,472
m3 RO / Ton Produksi
3,179
Kenaikan ratio Konsumsi listrik
Kenaikan ratio penggunaan nitrogen
Ratio penggunaan air PDAM
kenaikan ratio Konsumsi Steam
Catatan :
- Nitrogen bertambah karena produksi Foamer
- Air PDAM Mengalami beberapa kali flow mater bermasalah